Identification, Évaluation et Amélioration des Éléments Importants pour la Sécurité (EIPS) dans les Installations Classées Hydrocarbures Application au Four Rebouilleur du Module MPP0 — SONATRACH Hassi R'Mel
Loading...
Date
Authors
Journal Title
Journal ISSN
Volume Title
Publisher
Université Amar Thelidji- Laghouat FACULTE : TECHNOLOGIE DEPARTEMENT : GÉNIE DES PROCÉDÉS
Abstract
This thesis focuses on the application of the Safety Important Elements (SIE/EIPS)
methodology to classified hydrocarbon installations, using the H401 reboiler furnace at the
MPP0 production module of the Hassi R'Mel gas complex (SONATRACH, Algeria) as a
case study. The research is structured in three chapters. The first chapter establishes the
conceptual, regulatory and methodological foundations of the EIPS approach, drawing on the
Algerian regulatory framework (Law No. 03-10 of July 19, 2003, Executive Decrees No. 06-
198 and 21-331) and international normative references (IEC 61511:2016, IEC 61508:2010,
OLF 070 guideline, SEVESO III Directive). It defines four EIPS classification typologies by safety function, physical nature, hazard controlled and SIL level and formalizes a fivephase identification and management methodology. The second chapter applies this
methodology to the H401 furnace: characterization of six major risk categories, structural
decomposition into four sub-systems (feed, control, alarm, SIS/ESD emergency shutdown),
identification and classification of seven EIPS, and qualitative assessment of the ESD system
Safety Integrity Level (SIL) using Fault Tree Analysis (FTA) with the GRIF software.
Results reveal that the 1oo1 non-dedicated architecture of SIS sensors is the limiting factor
preventing attainment of the target SIL 2 level. The third chapter formalizes seven rated
reservations (two Critical, three Major, two Minor) and develops an 18-month structured
corrective action plan (CAP), incorporating alternative EIPS, designated responsible parties
and deadlines. Post-CAP re-evaluation projects the H401 ESD system toward the global SIL
2 target level, pending quantitative validation and third-party independent certification.
Description
Ce mémoire applique la démarche des Éléments Importants pour la Sécurité (EIPS) au four
rebouilleur H401 (complexe gazier Hassi R'Mel, Algérie). Le premier chapitre pose le cadre
réglementaire algérien (loi 03-10, décrets 06-198, 21-331) et international (IEC 61511, OLF
070, SEVESO III), et définit la méthodologie EIPS en cinq phases. Le deuxième chapitre
identifie sept EIPS sur le four H401 et évalue qualitativement le niveau SIL du système ESD
par arbre de défaillances (logiciel GRIF), révélant que l'architecture 1oo1 non dédiée des
capteurs SIS limite l'atteinte du SIL 2 cible. Le troisième chapitre formalise sept réserves
(deux Critiques, trois Majeures, deux Mineures) et élabore un plan d'actions correctives sur
18 mois. La réévaluation post-PAC projette le système ESD vers le niveau SIL 2 global, sous
réserve d'une validation quantitative et d'une certification par un organisme tiers.